Technical reference

Hardware and software details for project planning. Final equipment and settings are confirmed in the proposal.

spotEQ Battery

Battery
Cell chemistryLithium iron phosphate (LFP)
Nominal voltage48 V DC
Module size5 kWh (48 V, 100 Ah)
System capacitySized per site, built from modules
Battery managementIntegrated BMS, reported to the inverter over CAN
Usable depth of dischargeSet in commissioning for the selected pack
Inverter and metering
TypeBidirectional battery inverter with site metering
PhasesSingle-phase or three-phase
Verified platformVictron MultiPlus-II, 48 V range
Site meterThree-phase meter on the main incomer (Victron VM-3P75CT)
Power ratingSized with the battery, stated in the proposal
Operation
Controlled byspotEQ Node, one-second interval
Plan sourcespotEQ Equaliser, 48 hours ahead in 15-minute steps
LimitsSite import, export and asset limits enforced on site
SolarExisting production is included in the site picture
Installation
EnclosureIndoor floor-standing cabinet
CoolingPer selected cabinet
Dimensions and weightGiven for the chosen configuration
Certificates and datasheetsSupplied with the proposal
Scope of deliveryCabinet, inverter, metering, electrical work, commissioning

Battery and inverter are selected per site. The rows in grey are fixed once the configuration is set. The verified platform is the equipment the control software is tested against today.

spotEQ Node

Hardware
EnclosureDIN rail, fanless
Operating temperature−20 °C to +60 °C
Supply12–24 V DC or Power over Ethernet
ProcessorARM64, four cores
Memory2 GB
Storage16 GB eMMC, two system partitions and a separate data partition
NetworkEthernet. Wi-Fi and mobile broadband optional
ClockBattery-backed real-time clock
SupervisionHardware watchdog
Key storageTPM 2.0 or equivalent secure element
Control
Control interval1 second
Meter reading1 second
Status to the EqualiserEvery 5 seconds
Measurements to the EqualiserEvery 60 seconds
Setpoint lease30 seconds. A setpoint that is not renewed expires
Manual overrideLimited to 60 minutes, then it expires by itself
FallbackHold last value, self-consumption (default) or idle
Interfaces on site
Inverter and meterModbus TCP through the Victron GX
EV chargingOCPP 1.6J, charger connects to the Node (in development)
Local interfaceWeb page on the unit, local network only
Local sign-inPassword unique to the unit, printed on the label
Connection to the Equaliser
ProtocolMQTT over TLS
DirectionOutbound only. No inbound ports towards the internet
AuthenticationCertificate at both ends, one certificate per unit
Software updatesSigned and verified before they are installed
Remote accessNo remote shell and no direct register writes
Local storage
DatabaseSQLite on the data partition
MeasurementsAt least 7 days at 60-second resolution
Events30 days
SchedulesThe current one and the last ten
Size limit500 MB, oldest measurements removed first

The first production units are being built. The hardware rows are the baseline every unit delivered to a customer site meets. EV charging over OCPP is specified and being implemented, and is marked in grey until it has run on site.

spotEQ Equaliser

Planning
Horizon48 hours
Resolution15 minutes
RecalculatedEvery 15 minutes, and on new prices, tariff changes or equipment changes
Maximum age accepted on site30 minutes
Coverage warningLess than 2 hours of remaining plan
Prices and tariff
Price sourceENTSO-E day-ahead prices
AreasNorwegian bidding zones
CurrencyNOK, converted from EUR with European Central Bank reference rates
Tariff modelSupplier markup, network energy periods, tax and VAT per interval
Capacity chargePrice per kW, calendar month
Sites without a tariffMarket price only, labelled as such
Monitoring
Shown per siteMeasured, forecast and planned power, battery level, projected saving
AlarmsOpen, acknowledged, resolved. Email for high and critical
Site offlineWarning after 2 minutes, high alarm after 5 minutes
Measurement retention90 days
Access and interfaces
InterfaceWeb browser, nothing to install
RolesOrganisation and site level. Installer access is time-limited
APIREST, versioned
Record of changesChanges, alarms and schedule status with time and user
Control of site equipmentOnly through validated schedules. No remote shell, no direct register writes

These are the settings the software runs with today. Alarm thresholds and retention periods can be adjusted per customer.